Mounting Instructions

Pre-curled Isogenopak® jacketing film is supplied in rolls of 25 m and 35 m in length with 1000 mm as the most common width. The Isogenopak® system is completed by a large variety of pre-molded bends, T-sections, caps, and cuffs supplied by a co-operation partner.
Mounting Instructions_Fitting of a pre-molded bend
Fitting of a pre-molded bend
First the insulator must be attached to the pipe without gaps. When using mineral wool sections, loose fill wool can be used to cover the bends and other shapes. The insulator has to be affixed to the pipe consistently.
Mounting Instructions_T-section
T-section
To attach the Isogenopak® jacketing we advise to start with the molded pieces, e.g. bends (1) and T-sections (2).
Mounting Instructions_Cutting of Isogenopak® with a guide rail
Cutting of Isogenopak® with a guide rail
For straight sections, Isogenopak® is cut from the roll according to the circumference to be clad, inclusive addition/allowance for overlap. Allow an extra 20-30 mm for overlapping. A guide rail for the cutter (3) has proven its worth.
Mounting Instructions_Fitting of Isogenopak® to a straight section
Fitting of Isogenopak® to a straight section
Because of the pre-curling, Isogenopak® clings around the insulated pipe (4) almost by itself. Just a little additional adjustment is required. The circumferential seams should overlap by about 20-30 mm as well.
Mounting Instructions_Closing longitudinal seams with plastic push-in rivets
Closing longitudinal seams with plastic push-in rivets
Isogenopak® is fixed along the longitudinal seams either by using plastic push-in rivets in distances of about 150 mm (5) or special solvent-based adhesive continuously along the seams (6).
Mounting Instructions_Longitudinal seam closed with special solvent-based adhesive
Longitudinal seam closed with special solvent-based adhesive